- Location
- A church in Farnham
- The job
- Fault diagnosis, full plant room rebuild and new heating for a round, high-ceilinged sanctuary
- Equipment
- Two Viessmann Vitodens 200-W 49kW boilers, low-loss header with pumped zones, five bespoke Smith’s fan convectors, Myson LST radiators
- Completed
- December 2021
The challenge
This church came to us with a heating system that had never really worked. A previous installation had put in a single 40kW combi boiler that simply couldn’t deliver the output a building of this size needs.
Its sealed circuit leaked so badly that the filling loop had to be left permanently open just to keep it running. An older boiler was still serving another part of the church on a separate open-vented circuit. Kinked plastic pipework, a faulty upstairs fan convector and a system that had never been balanced left several areas permanently cold.
The biggest problem was the Sanctuary: a round room with a very high ceiling and large windows. Its radiators could never put out anywhere near the heat that room needs. Tracer gas testing then found multiple leaks in the old pipework under the Sanctuary floor.
What we did
Before removing anything, we surveyed the whole system and labelled every pipe (flow, return, bypass, hot water and redundant) so the new design would serve every part of the building.
- Removed both old boilers and rebuilt the plant room around two Viessmann Vitodens 200-W 49kW boilers (98kW combined) on a steel floor frame. If one is ever down, the other keeps the church warm.
- Set up boiler sequencing and weather compensation through the Viessmann controls, so the boilers share the load and flow temperatures follow the weather outside.
- Fitted a new low-loss header with separately pumped zones for the Sanctuary, ground floor hall, reception, first floor and hot water, plus a secondary hot water return.
- Added Spirotech air and dirt separators, a chemical dosing pot, a pressurisation unit and new expansion vessels, giving one sealed system with no more open filling loop.
- Took out the church’s existing BOSS unvented cylinder, relocated it and reinstalled it into the new layout.
- Ran a new 35mm gas supply with gas detection linked to an automatic isolation valve, and insulated every pipe with Kingspan Kooltherm.
- Worked with Smith’s to have five bespoke fan convectors made for the curved Sanctuary walls.
- Chased the Sanctuary floor for all-new insulated pipework to each convector, abandoning the corroded, leaking pipes, then backfilled and made good.
- Built a manifold under the stage, pressure tested on site, with every circuit labelled and given its own isolation, strainer and balancing valve.
- Replaced three foyer and reception radiators with Myson low surface temperature radiators and new TRVs, so they are safe to touch in busy public areas.
- Repaired the kinked pipework and the upstairs fan convector, then balanced the whole system.
All the work was carried out out of hours, under COVID restrictions, so church life could carry on as normal. The system was commissioned jointly with Viessmann, electrically certified and registered with the manufacturer and Building Control, and we finished with a full handover of the controls and plant room.
The result
Every radiator in the church now heats up, including areas that had been cold for years. The Sanctuary finally reaches temperature, the system holds its pressure without a filling loop left open, and the plant room is tidy, labelled and fully documented, with two boilers for back-up.
We have serviced the boilers since, stripping the burners, cleaning the heat exchangers and checking the expansion vessels.


Photos from the job









Looking after a church, school, office or other building with heating that never quite works? Take a look at our commercial heating and cooling service, or ask us for a quote and we’ll come and take a proper look.